Acrel DTSD1352

Mwongozo wa Mtumiaji wa Kipima Nishati cha Awamu Tatu cha Acrel DTSD1352

Model: DTSD1352 | Brand: Acrel (Manufactured by TGLGTQPX)

1. Utangulizi

This manual provides comprehensive instructions for the installation, operation, and maintenance of the Acrel DTSD1352 Three Phase Bidirectional Energy Meter. This device is designed for accurate measurement of three-phase energy consumption and generation, featuring RS485 communication for integration into monitoring systems. Please read this manual thoroughly before installation and operation to ensure safe and efficient use.

2. Taarifa za Usalama

ONYO: Hatari ya Mshtuko wa Umeme!

  • Ufungaji na matengenezo inapaswa kufanywa tu na wataalamu wa umeme waliohitimu.
  • Ensure all power is disconnected before installing or servicing the meter.
  • Do not touch live terminals.
  • Verify correct wiring connections to prevent damage to the meter or electrical system.
  • The meter must be installed in a dry, well-ventilated area, free from excessive dust, corrosive gases, and direct sunlight.

3. Bidhaa Imeishaview

The Acrel DTSD1352 is a compact and robust three-phase multi-function energy meter. It features a clear LCD display for real-time data, intuitive control buttons, and various connection terminals.

Mbele view of the Acrel DTSD1352 energy meter showing the LCD display, control buttons, and terminal connections.

Kielelezo cha 3.1: Mbele view of the DTSD1352 meter. This image displays the main LCD screen showing power readings (e.g., 0.00 kW), the "SET" button, and three orange arrow buttons for navigation. Terminal blocks are visible at the top and bottom for electrical connections.

Mwenye pembe view of the Acrel DTSD1352 energy meter, showing the side profile and additional terminal details.

Kielelezo cha 3.2: Mwenye pembe view of the DTSD1352 meter. This perspective highlights the compact design and the various input/output terminals on the top and bottom, as well as the side labeling for model identification.

4. Vipimo

The following table outlines the key technical specifications of the Acrel DTSD1352 energy meter. For detailed information, refer to the product datasheet.

Table of technical specifications for the Acrel DTSD1352 energy meter, including voltage, current, measurement performance, pulse, communication, outline, and environment details.

Kielelezo cha 4.1: Detailed technical specifications. This image presents a table covering various parameters such as reference voltage (3*57.7/100V, 3*220/380V, 3*380V), reference frequency (50Hz), maximum current (6A, 80A), accuracy (Class 0.5S), communication interface (RS485, MODBUS-RTU), dimensions (127*88*70 mm), and environmental conditions (operating temperature -25~55℃, humidity ≤95%).

Jedwali 4.1: Maelezo ya Jumla
KigezoThamani
Rejea Voltage3*57.7/100V, 3*220/380V, 3*380V
Masafa ya Marejeleo50Hz
Upeo wa Sasa6A, 80A (depending on model)
Accuracy of active kWhDarasa la 0.5S
Kiolesura cha MawasilianoRS485
Itifaki ya MawasilianoMODBUS-RTU
Vipimo (L*W*H)127mm * 88mm * 70mm
Joto la Uendeshaji-25 ℃ hadi 55 ℃
Joto la Uhifadhi-40 ℃ hadi 70 ℃
Unyevu≤95% (Hakuna ufupishaji)
Mwinuko<2000m
Uzito wa KipengeeWakia 7.1 (takriban 200g)

5. Ufungaji na Wiring

Proper installation and wiring are critical for the accurate and safe operation of the DTSD1352 meter. Refer to the diagrams below for connection methods.

Wiring diagrams for the Acrel DTSD1352 energy meter, showing both direct connection (3P4W) and connection via Current Transformers (CTs).

Kielelezo cha 5.1: Wiring diagrams. This image illustrates two primary wiring methods: a 3-phase 4-wire (3P4W) direct connection where power lines (A, B, C, N) connect directly to the meter, and a connection via Current Transformers (CTs) for higher current applications, showing the CTs connected to the respective phase lines and then to the meter.

5.1 Direct Connection (3P4W)

For direct connection, ensure the phase lines (A, B, C) and neutral (N) are connected to the corresponding terminals on the meter. This method is typically used for lower current applications where the meter can directly handle the load current.

  • Connect Phase A to terminal 'A'.
  • Connect Phase B to terminal 'B'.
  • Connect Phase C to terminal 'C'.
  • Connect Neutral to terminal 'N'.
  • Hakikisha miunganisho yote ni salama na imewekewa maboksi ipasavyo.

5.2 Connection via Current Transformers (CTs)

For higher current applications, the DTSD1352 meter can be connected via external Current Transformers (CTs). This method scales down the current to a measurable level for the meter.

  • Install the CTs on each phase line (A, B, C).
  • Connect the secondary windings of the CTs to the corresponding current input terminals (e.g., Ia*, Ia, Ib*, Ib, Ic*, Ic) on the meter.
  • Ensure the polarity of the CTs is correct (P1/K to the source side, P2/L to the load side, and S1/S2 to the meter). Incorrect polarity will result in inaccurate readings.
  • Unganisha juzuutage inputs (Ua, Ub, Uc, N) directly from the respective phases and neutral to the meter.
  • It is recommended to install a fuse on the voltage input lines for protection.

Important: Always ensure the CT secondary circuit is closed before applying power to the primary circuit. Never open the secondary circuit of a live CT.

6. Uendeshaji

Once installed and powered, the DTSD1352 meter will automatically begin measuring. The LCD display shows various parameters, which can be navigated using the control buttons.

6.1 Urambazaji wa Onyesho

  • Onyesho la LCD: Shows real-time measurements such as voltage, current, active power, reactive power, power factor, frequency, and total energy (kWh).
  • "SET" Button: Used to enter the parameter setting mode or confirm selections.
  • Arrow Buttons (Left, Right, Up, Down): Used to navigate through different display screens or adjust parameter values in setting mode.

6.2 Reading Energy Data

Press the arrow buttons to cycle through the various measurement screens. Common readings include:

  • Total Active Energy (kWh)
  • Forward Active Energy (kWh)
  • Reverse Active Energy (kWh)
  • Voltage (V) per phase
  • Current (A) per phase
  • Active Power (kW) per phase and total
  • Reactive Power (kVar) per phase and total
  • Kiwanda cha Nguvu (PF)
  • Mara kwa mara (Hz)

6.3 RS485 Mawasiliano

The meter supports RS485 communication with MODBUS-RTU protocol. This allows for remote reading of meter data and configuration. Refer to the MODBUS communication protocol document for detailed register addresses and commands.

7. Matengenezo

The DTSD1352 energy meter is designed for long-term, reliable operation with minimal maintenance. However, periodic checks are recommended.

  • Kusafisha: Keep the meter clean and free from dust. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.
  • Viunganisho: Periodically check all wiring connections to ensure they are tight and secure. Loose connections can lead to inaccurate readings or overheating.
  • Mazingira: Hakikisha mazingira ya kufanya kazi yanabaki ndani ya safu maalum za joto na unyevu.
  • Urekebishaji: Kipima kimepimwa kiwandani. Ukishuku kuwa kuna makosa, wasiliana na wafanyakazi wa huduma waliohitimu kwa ajili ya urekebishaji upya.

8. Utatuzi wa shida

This section provides solutions to common issues you might encounter with the DTSD1352 meter.

Jedwali 8.1: Mwongozo wa Utatuzi
TatizoSababu inayowezekanaSuluhisho
Meter display is blank.Hakuna usambazaji wa umeme kwenye mita.Check the main power supply and wiring connections to the meter's voltage input terminals. Ensure fuses are intact.
Inaccurate energy readings.Incorrect wiring, incorrect CT ratio setting (if applicable), faulty CTs, or meter malfunction.Verify all wiring connections according to Section 5. Ensure CT polarity is correct. Check if the CT ratio programmed in the meter matches the physical CTs. If issues persist, contact technical support.
Kushindwa kwa mawasiliano ya RS485.Incorrect wiring of RS485 terminals (A/B), incorrect communication parameters (baud rate, parity, address), or software issue.Check RS485 A and B terminal connections. Verify communication settings (baud rate, data bits, stop bits, parity, meter address) in your master device match the meter's settings. Ensure proper termination resistors are used if necessary.
Meter shows "Error" or specific error codes.Hitilafu ya ndani au tatizo maalum la uendeshaji.Note down the error code and consult the full product manual or contact technical support for specific error code interpretations and solutions.

9. Udhamini na Msaada

This product is manufactured by TGLGTQPX and sold under the Acrel brand. For specific warranty terms and conditions, please refer to the documentation provided at the time of purchase or contact your vendor. General support for the Acrel DTSD1352 meter can be obtained through the manufacturer's official channels or your authorized distributor.

For technical assistance, troubleshooting beyond this manual, or spare parts, please contact:

  • Mtengenezaji: TGLGTQPX
  • Chapa ya Bidhaa: Ekari
  • Mfano: DTSD1352
  • (Contact information such as website or email would typically be provided here by the manufacturer.)

Nyaraka Zinazohusiana - DTSD1352

Kablaview ADL100-ET Ufungaji na Mwongozo wa Maagizo ya Uendeshaji wa Mita ya Umeme ya Awamu Moja
Mwongozo wa kina wa ufungaji na uendeshaji wa mita ya umeme ya awamu moja ya Acrel ADL100-ET. Mwongozo huu unaelezea maelezo ya kiufundi, maelezo ya kazi, maagizo ya wiring, menyu ya kuonyesha, taratibu za programu, na itifaki za mawasiliano (Modbus RTU).
Kablaview Acrel ADL3000-E Smart Meter: Ufungaji na Mwongozo wa Uendeshaji
Maagizo ya kina ya usakinishaji na uendeshaji wa mita mahiri ya Acrel ADL3000-E, inayofunika vipimo vya kiufundi, nyaya, vitendaji vya kuonyesha na itifaki za mawasiliano.
Kablaview Kifaa cha Umeme chenye Kazi Nyingi cha Aina ya Reli cha Acrel ACR10R chenye Kibadilishaji cha Mkondo wa Nje cha Kiini Kilichogawanyika - Mwongozo wa Matumizi na Usakinishaji
This manual provides comprehensive instructions for the Acrel ACR10R series rail-type multifunction electrical instrument, including its specifications, functions, installation, programming, and RS485 MODBUS-RTU communication. It details technical parameters, connection modes, operation procedures, and troubleshooting guidance for industrial and commercial power monitoring applications.
Kablaview ATE 系列无线测温传感器安装说明 V1.7
本说明书详细介绍了 ATE系列无线测温传感器的产品概述、型号说明、技术指标、安装方法以及注意事项,K适3户内开关柜 na 0.4kV kwa kutumia gia.
Kablaview Mfululizo wa Acrel ATE Maagizo ya Ufungaji wa Sensor ya Joto Isiyo na waya V1.9
Hati hii inatoa maagizo ya usakinishaji wa vihisi joto visivyotumia waya vya mfululizo wa Acrel ATE, vinavyofunika bidhaa juuview, utangulizi wa aina, vipengele vya kiufundi, mbinu za usakinishaji wa miundo mbalimbali (ATE100M, ATE100, ATE200, ATE400), na waratibu wa halijoto isiyotumia waya (ATC450-C, ATC600). Inafafanua maelezo, taratibu za usakinishaji, na tahadhari muhimu za kutumia vitambuzi hivi kwenye swichi ya umeme.