EARU EARU-1008

EARU Electric 440V 63A 3-Awamu ya VoltagMwongozo wa Maelekezo ya Kinga ya Mkondo wa Juu na Elektroniki

Model: EARU-1008

1. Utangulizi

This manual provides comprehensive instructions for the installation, operation, and maintenance of the EARU Electric 3-Phase Voltage and Overcurrent Protector, Model EARU-1008. This device is designed to safeguard 3-phase electrical systems by continuously monitoring voltage and current, offering protection against over-voltage, chini ya voltage, overcurrent, and phase failure. It is suitable for industrial and commercial applications requiring reliable electrical monitoring and protection.

2. Taarifa za Usalama

ONYO: Hatari ya mshtuko wa umeme. Ufungaji na matengenezo yanapaswa kufanywa na wafanyakazi waliohitimu pekee.

  • Daima ondoa umeme kabla ya kusakinisha au kuhudumia kifaa.
  • Hakikisha kuweka msingi mzuri ili kuzuia mshtuko wa umeme.
  • Hakikisha miunganisho yote ya nyaya ni salama na sahihi kulingana na mchoro wa nyaya.
  • Usitumie kifaa ikiwa kinaonekana kuharibiwa.
  • Kuzingatia kanuni zote za umeme za ndani na za kitaifa.

3. Bidhaa Imeishaview

3.1. Sifa Muhimu

  • Real-time 3-Phase Monitoring: Displays live voltage (L1, L2, L3) and current (L1, L2, L3) values.
  • Ulinzi kamili: Ulinzi dhidi ya kuzidishatage, chini ya voltage, overcurrent, and phase failure.
  • Vigezo Vinavyoweza Kurekebishwa: User-configurable settings for protection thresholds and recovery delays.
  • Automatic Phase Failure Reset: Detects and automatically resets after phase anomalies.
  • High-Visibility LED Display: Bright red LED for clear readings in various lighting conditions.
  • Mlima wa Reli ya DIN: Easy integration into standard electrical panels.
  • Clear Terminal Labeling: Simplified installation with clearly marked input and output terminals.

3.2. Vipengele na Onyesho

The device features a clear LED display and intuitive control buttons for configuration. The display shows real-time voltage and current for each phase, along with indicators for protection status.

EARU Electric Voltage Protector Display and Controls

Picha ya 3.2.1: Mbele view of the EARU Electric Voltage Protector, showing the LED display for L1, L2, L3 voltage and current, along with control buttons (SET, Up, Down, Power) and protection indicators. Terminal labels for N, L1, L2, L3 (IN and OUT) are also visible.

EARU Electric Voltage Protector Product Features and Terminals

Picha ya 3.2.2: A perspective view highlighting the product features and the input/output terminals (N, L1, L2, L3) at the top and bottom of the device. This image emphasizes the physical layout and connection points.

4. Kuweka na Kuweka

4.1. Kuweka

The EARU-1008 is designed for DIN rail mounting. Securely attach the device to a standard 35mm DIN rail within an electrical enclosure.

4.2. Viunganisho vya Wiring

Refer to the wiring diagram below for correct connections. Ensure all connections are tight and properly insulated.

  1. Connect the incoming neutral (N) and phase lines (L1, L2, L3) to the 'IN' terminals.
  2. Connect the outgoing neutral (N) and phase lines (L1, L2, L3) to the 'OUT' terminals.
  3. Angalia miunganisho yote mara mbili kabla ya kutumia nishati.
EARU Electric Voltage Protector Wiring Diagram

Picha ya 4.2.1: Detailed wiring diagram for the EARU Electric Voltage Protector, showing connections for N, L1, L2, L3 for both input and output. The diagram illustrates how to integrate the protector into a 3-phase electrical system.

5. Maagizo ya Uendeshaji

5.1. Nguvu-Up ya Awali

Once wired, apply power to the device. The LED display will illuminate, showing the real-time voltage and current for each phase.

5.2. Viashiria vya Maonyesho

  • V: Voltage kuonyesha.
  • A: Onyesho la sasa.
  • Nguvu: Output indication.
  • >V: Zaidi ya voltage dalili.
  • <V: Chini ya voltage dalili.
  • > mimi: Over-current indication.

5.3. Kuweka Vigezo

Use the 'SET' button to enter the configuration menu and the 'Up' and 'Down' keys to adjust values. Press 'SET' again to confirm and move to the next parameter. Hold 'SET' for 3 seconds to enter settings mode.

EARU Electric Voltage Protector Setting Parameters

Picha ya 5.3.1: A detailed guide to setting various protection parameters on the EARU Electric Voltage Protector. This includes overvoltage, bila kujalitage, overcurrent, and recovery delay settings, with default values and adjustment ranges.

Key adjustable parameters include:

  • Kupindukiatage Mipangilio ya Ulinzi: Range 230-300V (Default 270V).
  • Kupindukiatage Protection Recover Setting: Range 225-295V (Default 265V).
  • Kupindukiatage Recovery Delay: Range 1-500s (Default 30s).
  • Kupindukiatage Trip Delay: Range 0.1-30s (Default 1.0s).
  • Ubora wa chinitage Mipangilio ya Ulinzi: Range 140-210V (Default 170V).
  • Ubora wa chinitage Protection Recover Setting: Range 145-215V (Default 175V).
  • Ubora wa chinitage Trip Delay: Range 0.1-30s (Default 1.0s).
  • Mpangilio wa Ulinzi wa Sasa hivi: Range 1-63A (Default 30A).
  • Overcurrent Trip Delay: Range 0.1-30s (Default 1.0s).
  • Voltage & Current Manual Error Calibration: Adjust for accuracy, range -9.5% to +9.5% (Default 0%).
  • Power-on Delay Setting: Adjustable Range: 1-500S (Default: 10s).

5.4. Mwongozo ON/OFF

The power button allows for manual switching of the device output.

6. Matengenezo

The EARU-1008 is designed for minimal maintenance. However, periodic checks are recommended:

  • Weka kifaa safi na bila vumbi na uchafu.
  • Periodically inspect wiring connections for tightness and signs of wear.
  • Hakikisha uingizaji hewa wa kutosha kuzunguka kifaa ili kuzuia joto kupita kiasi.

7. Utatuzi wa shida

Ikiwa kifaa hakifanyi kazi kama ilivyotarajiwa, fikiria yafuatayo:

  • Hakuna Onyesho/Hakuna Nguvu: Check the main power supply and all wiring connections.
  • Protection Trip: Identify the active protection indicator (>V, <V, >I). Check the corresponding voltage or current levels. The device will automatically reset once conditions return to normal, based on configured recovery delays.
  • Phase Failure: The device automatically detects and responds to phase failures, initiating a cut-off and auto-reset once the phase is restored.
  • Usomaji usio sahihi: If readings appear inaccurate, consider performing a manual error calibration as described in Section 5.3.
EARU Electric Voltage Protector Protection Features

Picha ya 7.1: This image highlights the various protection features of the EARU Electric Voltage Protector, including phase failure cut-off, low voltage cut-off, high voltage cut-off, overload cut-off, phase sequence cut-off, and auto-reset on normal conditions. These are key aspects for troubleshooting protection trips.

8. Vipimo

KigezoThamani
ChapaEARU
MfanoEARU-1008
Iliyokadiriwa Ugavi VoltageAC 3*220V (N-L1/L2/L3) / 440V
Mara kwa mara Iliyokadiriwa50/60Hz
Over Current Protection Setting Range1-63A (Default 30A)
Zaidi ya Voltage Protection Setting Range230-300V (Default 270V)
Chini ya Voltage Protection Setting Range140-210V (Default 170V)
Vipimo vya Bidhaa20 x 10 x 20 cm
Uzito wa Kipengee450 g
Aina ya KuwekaDIN Reli
EARU Electric Voltage Protector Dimensions and Technical Specifications

Picha ya 8.1: This image provides a visual representation of the EARU Electric Voltage Protector's dimensions and a table of key technical specifications, including voltage, frequency, and protection ranges.

9. Udhamini na Msaada

9.1. Udhamini

The EARU Electric Voltage Protector (Model EARU-1008) comes with a Udhamini wa mtengenezaji wa mwaka 1 kuanzia tarehe ya ununuzi, ikishughulikia kasoro katika vifaa na ufundi chini ya matumizi ya kawaida. Tafadhali weka uthibitisho wako wa ununuzi kwa madai ya udhamini.

9.2. Msaada kwa Wateja

For technical assistance, troubleshooting, or warranty inquiries, please contact EARU customer support through your retailer or the official EARU website. Provide your model number (EARU-1008) and a detailed description of the issue for efficient service.